Verify Absence of Voltage
Sequence a qualified-person absence-of-voltage verification before work begins.
The disconnect is open and locked, but there may be backfeed from a temporary generator. The exposed terminal block cannot be treated as de-energized until a qualified person verifies absence of voltage. Live-dead-live verification: prove the tester, test the circuit, prove the tester again. The common trap is treating a dark indicator light, quiet motor, or open disconnect as proof. Those are clues, not verification. A failed lamp, wrong source, induced voltage, or backfeed can leave the worker exposed while everyone believes the job is safe. Prove tester Inspect the meter and leads, select the correct function/range, and verify the…